15. USING A DIRECT DRIVE MOTOR
15 - 8
(b) Magnetic pole detection by the minute position detection method
Is the moving distance
during the magnetic pole
detection acceptable?
(Note 3)
Turn the servo amplifier power off and on again.
Execute "Forward rotation" or "Reverse rotation" with "Positioning operation" in the test operation
mode on MR Configurator2. Set the moving distance to "0" at this time.
Set [Pr. PL08 Linear servo motor/DD motor function selection 3] to "_ _ _ 4" to set the magnetic pole
detection method to "Minute position detection method".
The magnetic pole detection is carried out.
Is the response of the
minute position detection method
of [Pr. PL17] the final value?
Has an abnormal sound or
vibration occurred during the
magnetic pole detection?
Decrease the response of the minute
position detection method of [Pr. PL17] by
two as the final setting value.
Increase the response of the minute
position detection method of [Pr. PL17] by
one.
Not
acceptable
YES
Acceptable
NO
YES
NO
Magnetic pole detection
End
Set [Pr. PL01] to "_ _ _ 0" to set "Magnetic pole detection invalid". (Note)
Check that FLS (Upper stroke limit), RLS (Lower stroke limit), and EM2 (Forced stop 2) are on, and
turn the servo amplifier power off and on again.
Set the test operation select switch (SW2-1) of the servo amplifier to "Up", and turn the servo
amplifier power off and on again.
Set [Pr. PL01 Linear servo motor/DD motor function selection 1] to "_ _ _ 1" to set "Magnetic pole
detection always valid". (Note)
Set the load inertia moment ratio of the direct drive motor with [Pr. PL17 Magnetic pole detection -
Minute position detection method - Function selection]. (Note 2)
1)
2)
3)
4)
5)
6)
7)
8)
Note 1.
2.
3.
For the incremental system, the [Pr. PL01] setting is not required.
If the load to direct drive motor inertia ratio is unknown, perform the magnetic pole detection by the
position detection method, and then perform the auto tuning to set an estimated value.
For the magnetic pole detection by the minute position detection method, the maximum rotation angle at
the magnetic pole detection must be five degrees or less. To shorten the travel distance, increase the
response by the minute position detection method in [Pr. PL17].
Turn "On (up)" the test operation select switch (SW2-1) of the servo amplifier, and then cycle the
power of the servo amplifier.
Set [Pr. PL01 Linear servo motor/DD motor function selection 1] to "_ _ _ 1" to set "Magnetic pole
detection always enabled". (Note)
Execute "Forward rotation" or "Reverse rotation" with "Positioning operation" in the test operation
mode on MR Configurator2. Set the travel distance to "0" at this time.
Is the response of the minute
position detection method set
by [Pr. PL17] finalized?
by
by
Is the travel distance
Set [Pr. PL01] to "_ _ _ 0" to set "Magnetic pole detection disabled". (Note)