11. Options and peripheral devices
11 - 11
11.2.3 parameter setting
Set [Pr. PA02] according to the option to be used.
Selection of regenerative option
00: Regenerative option is not used.
For servo amplifier of 100 W, regenerative resistor is not used.
For servo amplifier of 0.2 kW to 7 kW, built-in regenerative
resistor is used.
01: FR-BU2/FR-RC/FR-CV
02: MR-RB032
03: MR-RB12
04: MR-RB32
05: MR-RB30
06: MR-RB50 (Cooling fan is reuired)
08: MR-RB31
09: MR-RB51 (Cooling fan is reuired)
0B: MR-RB3N
0C: MR-RB5N (Cooling fan is reuired)
00
[Pr. PA02]
11.2.4 Connection of regenerative option
POINT
When the MR-RB50, MR-RB51, or MR-RB5N is used, a cooling fan is required
to cool it. The cooling fan should be prepared by the customer.
For the sizes of wires used for wiring, refer to section 11.9.
The regenerative option generates heat of 100 °C higher than the ambient temperature. Fully consider heat
dissipation, installation position, used wires, etc. to place the option. For wiring, use flame-resistant wires or
make the wires flame-resistant and keep them away from the regenerative option. Always use twisted cables
of max. 5 m length for connection with the servo amplifier.