1. Specifications
1
12
3
4
5
I-34
1-2 Major Component Specifications
(A) Indoor Units : 4-Way Air Discharge Semi-concealed Type
MODEL No. ASR 425 H
Source 220 - 230 - 240 V / 1 phase / 50Hz
Controller P.C.B. Ass’y CR-X253GH (Microprocessor)
Fan (Number…diameter) mm Turbo (1 … ø 490)
Fan motor
Model…Nominal output W SFG6X-41A5P … 40 W
Source 220 - 230 - 240 V / 1 phase / 50 Hz
No. of pole…r.p.m. (230 V, High) rpm. 6 … 470
Coil resistance BRN WHT : 114.0 ORG YEL : 66.4
(Ambient temperature 20°C) WHT VLT : 23.9 WHT PNK : 77.4
VLT ORG : 12.4 YEL BLK : 82.1
Safety device
Operating temperature Open °C 130 ± 8
Close °C(79± 15 )
Run capacitor VAC, µF 440 V , 4 µF
Electronic expansion valve
Coil DKV-MOZS582E0
Coil resistance (at 20°C) ORG GRY : 46, YEL GRY : 46
RED GRY : 46, BLK GRY : 46
Valve body IKV-24D12
Heat exchanger
Coil Aluminum plate fin / Copper tube
Rows…fin pitch mm 2 … 1.5
Face area m
2
0.295
Panel
Model No. ASG 0025
Dew proof heater 240 V, 26 W
Auto louver motor M2LB24ZA12
Auto louver motor…Rated V, W, rpm. 240 VAC, 3W, 2.5 rpm
Coil resistance (at 25 °C) 15.620 ± 15 %
Drain Pump WP20SL - 21
Rated VAC, W AC230 V, 50 Hz, 14.7 W
Total head & capacity 400 mm, 600 cc/min