1. Specifications
1
12
3
4
5
I-14
1-1 Unit Specifications
Ceiling Mounted Type
MODEL No. Indoor Unit ACR 425 H
Outdoor Unit AER 425 SHLE
POWER SOURCE 220 - 230 - 240 V / 1 phase / 50 Hz
PERFORMANCE Cooling Heating
Capacity kW 7.3 8.6
BTU / h 25,000 29,300
Air circulation (Hi / Me / Lo) m
3
/h 1,080 / 960 / 840
Moisture removal (High) Liters/h 3.5
ELECTRICAL RATINGS
Voltage rating V 220 230 240 220 230 240
Available voltage range V 198 – 264 198 – 264
Running amperes* A 13.15 13.27 13.38 14.65 14.58 14.49
Max. running amperes** A 14.49 14.53 14.56 16.55 16.38 16.19
Power input kW 2.77 2.89 2.95 3.06 3.13 3.19
Power factor % 95.7 94.7 91.9 94.9 93.3 91.7
C.O.P W / W 2.64 2.53 2.47 2.81 2.75 2.7
Max. starting amperes A 69 72 75 69 72 75
FEATURES
Controls / Thermostat control Microprocessor / I.C. thermostat
Timer ON / OFF 72-hours ON/OFF 24-hours & Program
Fan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)
Airflow direction (Indoor) Automatic (Remote control)
Air filter Washable, easy access, long life (2,500 hr)
Remote controller (Option) Wired : REM HW A Wireless : REM HL A
Refrigerant control Electronic expansion valve
Drain pump (Drain connection) No (20A, OD26 mm)
Compressor Rotary (Sanyo)
Operation sound
Indoor - Hi/Me/Lo
dB - A 39 / 37 / 34
Outdoor - Hi
dB - A 52
Color (Approximate value) Indoor Munsell 10Y9.3 / 0.4, RAL 9010-GL
Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GL
REFRIGERANT TUBING
Limit of tubing length m (ft.) 50 (164 )
Limit of tubing length at shipment m (ft.) 30 ( 98 )
Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)
between the two units Outdoor unit is lower than indoor unit : 30 (98)
Refrigerant tube Narrow tube mm (in.) 6.35 (1 / 4)
outer diameter Wide tube mm (in.) 15.88 (5 / 8)
Refrigerant amount at shipment kg R407C - 3.2
DIMENSIONS & WEIGHT Indoor unit Outdoor unit
Unit dimensions Height mm (in.) 190 ( 7 - 15 / 32) 735 (28 - 30 / 32)
Width mm (in.) 1,300 (51 - 6 / 32) 940 (37 )
Depth mm (in.) 670 (26 - 12 / 32) 340 (13 - 12 / 32)
Package dimensions Height mm (in.) 266 (10 - 15 / 32) 826 (32 - 17 / 32)
Width mm (in.) 1,403 (55 - 8 / 32) 1,016 (40 )
Depth mm (in.) 789 (31 - 2 / 32) 416 (16 - 12 / 32)
Net weight kg (lb.) 26 ( 57) 71 ( 157)
Shipping weight kg (lb.) 32 ( 71) 77 ( 170)
Shipping volume
m
3
(cu. ft)
0.294 (10.4) 0.349 (12.3)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Cooling:
Rating conditions (*): Indoor air temperature 27 °CDB/19 °C WB, Outdoor air temperature 35 °C DB
Full load conditions (**): Indoor air temperature 32 °CDB/23 °C WB, Outdoor air temperature 43 °C DB
Heating:
Rating conditions (*): Indoor air temperature 20 °C DB, Outdoor air temperature 7 °C DB / 6 °C WB
Full load conditions (**): Indoor air temperature 24 °C DB, Outdoor air temperature 24 °C DB / 15.5 °C WB