1. Specifications
1
2
3
4
5
I-33
SM8008
1-1Unit Specifications
Concealed Duct Type
MODEL No. Indoor Unit ADR 448 H
Outdoor Unit AER 448 SHL3E
POWER SOURCE 380 - 400 - 415 V / 3N / 50 Hz
PERFORMANCE Cooling Heating
Capacity kW 12.6 15.3
BTU / h 43,000 52,200
Air circulation (Hi / Me / Lo) m
3
/h 1,980 / 1,800 / 1,500
Moisture removal (High) Liters/h 5.4
External static pressure (High)
mmAq(Pa)
8.0 (78) : at shipment, 11.5 (113) : using the booster cable
ELECTRICAL RATINGS
Voltage rating V 380 400 415 380 400 415
Available voltage range V 342 – 456 342 – 456
Running amperes* A 8.49 8.49 8.51 9.69 9.69 9.71
Max. running amperes** A 9.62 9.62 9.63 10.20 10.20 10.21
Power input kW 4.71 4.76 4.79 5.62 5.66 5.70
Power factor % 84.3 80.9 78.3 88.1 84.3 81.7
C.O.P W / W 2.68 2.65 2.63 2.72 2.7 2.68
Max. starting amperes A 53 56 58 53 56 58
FEATURES
Controls / Thermostat control Microprocessor / I.C. thermostat
Timer ON / OFF 72-hours
Fan speeds Indoor / Outdoor 3 and Automatic control / 2 (Auto)
Airflow direction (Indoor)
Air filter Field supply
Remote controller (Option) Wired : REM HW A
Refrigerant control Electronic expansion valve
Drain pump (Drain connection) Max. head 75 cm above unit bottom (25A, OD32 mm)
Compressor Scroll (Sanyo)
Operation sound
Indoor - Hi/Me/Lo
dB - A 40 / 37 / 33, (44 / 40 / 37 : using the booster cable)
Outdoor - Hi
dB - A 55
Color (Approximate value) Indoor
Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GL
REFRIGERANT TUBING
Limit of tubing length m (ft.) 50 (164 )
Limit of tubing length at shipment m (ft.) 30 ( 98 )
Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)
between the two units Outdoor unit is lower than indoor unit : 30 (98)
Refrigerant tube Narrow tube mm (in.) 9.52 (3 / 8)
outer diameter Wide tube mm (in.) 19.05 (3 / 4)
Refrigerant amount at shipment kg R407C - 4.5
DIMENSIONS & WEIGHT Indoor unit Outdoor unit
Unit dimensions Height mm (in.) 310 (12 - 7 / 32) 1,235 (48 - 20 / 32)
Width mm (in.) 1,480 ( 58 - 9 / 32) 940 (37 )
Depth mm (in.) 630 (24 - 26 / 32) 340 (13 - 12 / 32)
Package dimensions Height mm (in.) 358 (14 - 3 / 32) 1,326 (52 - 7 / 32)
Width mm (in.) 1,671 ( 65 - 25 / 32) 1,016 (40 )
Depth mm (in.) 783 (30 - 26 / 32) 416 (16 - 12 / 32)
Net weight kg (lb.) 47 ( 104) 108 ( 238)
Shipping weight kg (lb.) 52 ( 115) 115 ( 254)
Shipping volume
m
3
(cu. ft)
0.468 (16.5) 0.56 (19.8)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Cooling:
Rating conditions (*): Indoor air temperature 27 °CDB/19 °C WB, Outdoor air temperature 35 °C DB
Full load conditions (**): Indoor air temperature 32 °CDB/23 °C WB, Outdoor air temperature 43 °C DB
Heating:
Rating conditions (*): Indoor air temperature 20 °C DB, Outdoor air temperature 7 °C DB / 6 °C WB
Full load conditions (**): Indoor air temperature 24 °C DB, Outdoor air temperature 24 °C DB / 15.5 °C WB