Sharp R-426H Service Manual Page 16

  • Download
  • Add to my manuals
  • Print
  • Page
    / 194
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 15
1. Specifications
1
2
3
4
5
I-11
1-1 Unit Specifications
Ceiling Mounted Type
MODEL No. Indoor Unit ACR 425 H
Outdoor Unit AER 425 SCL3E
POWER SOURCE 380 - 400 - 415 V / 3N / 50 Hz
PERFORMANCE Cooling
Capacity kW 7.3
BTU / h 25,000
Air circulation (Hi / Me / Lo) m
3
/h 1,080 / 960 / 840
Moisture removal (High) Liters/h 3.5
ELECTRICAL RATINGS
Voltage rating V 380 400 415
Available voltage range V 342 – 456
Running amperes* A 4.77 4.72 4.67
Max. running amperes** A 5.62 5.63 5.64
Power input kW 2.72 2.75 2.77
Power factor % 86.6 84.1 82.5
C.O.P W / W 2.68 2.65 2.64
Max. starting amperes A 27 29 30
FEATURES
Controls / Thermostat control Microprocessor / I.C. thermostat
Timer ON / OFF 72-hours ON/OFF 24-hours & Program
Fan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)
Airflow direction (Indoor) Automatic (Remote control)
Air filter Washable, easy access, long life (2,500 hr)
Remote controller (Option) Wired : REM HW A Wireless : REM CLR A
Refrigerant control Electronic expansion valve
Drain pump (Drain connection) No (20A, OD26 mm)
Compressor Rotary (Sanyo)
Operation sound
Indoor - Hi/Me/Lo
dB - A 39 / 37 / 34
Outdoor - Hi
dB - A 52
Color (Approximate value) Indoor Munsell 10Y9.3 / 0.4, RAL 9010-GL
Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GL
REFRIGERANT TUBING
Limit of tubing length m (ft.) 50 (164 )
Limit of tubing length at shipment m (ft.) 30 ( 98 )
Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)
between the two units Outdoor unit is lower than indoor unit : 30 (98)
Refrigerant tube Narrow tube mm (in.) 6.35 (1 / 4)
outer diameter Wide tube mm (in.) 15.88 (5 / 8)
Refrigerant amount at shipment kg R407C - 3.2
DIMENSIONS & WEIGHT Indoor unit Outdoor unit
Unit dimensions Height mm (in.) 190 ( 7 - 15 / 32) 735 (28 - 30 / 32)
Width mm (in.) 1,300 (51 - 6 / 32) 940 (37 )
Depth mm (in.) 670 (26 - 12 / 32) 340 (13 - 12 / 32)
Package dimensions Height mm (in.) 266 (10 - 15 / 32) 826 (32 - 17 / 32)
Width mm (in.) 1,403 (55 - 8 / 32) 1,016 (40 )
Depth mm (in.) 789 (31 - 2 / 32) 416 (16 - 12 / 32)
Net weight kg (lb.) 26 ( 57) 69 ( 152)
Shipping weight kg (lb.) 32 ( 71) 75 ( 165)
Shipping volume
m
3
(cu. ft)
0.294 (10.4) 0.349 (12.3)
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Cooling:
Rating conditions (*): Indoor air temperature 27 °CDB/19 °C WB, Outdoor air temperature 35 °C DB
Full load conditions (**): Indoor air temperature 32 °CDB/23 °C WB, Outdoor air temperature 43 °C DB
Page view 15
1 ... 15 16 17 ... 194

Comments to this Manuals

No comments