1. Specifications
1
12
3
4
5
I-16
1-1 Unit Specifications
Ceiling Mounted Type
DATA SUBJECT TO CHANGE WITHOUT NOTICE.
Cooling:
Rating conditions (*): Indoor air temperature 27 °CDB/19 °C WB, Outdoor air temperature 35 °C DB
Full load conditions (**): Indoor air temperature 32 °CDB/23 °C WB, Outdoor air temperature 43 °C DB
Heating:
Rating conditions (*): Indoor air temperature 20 °C DB, Outdoor air temperature 7 °C DB / 6 °C WB
Full load conditions (**): Indoor air temperature 24 °C DB, Outdoor air temperature 24 °C DB / 15.5 °C WB
MODEL No. Indoor Unit ACR 436 H
Outdoor Unit AER 436 SHL3E
POWER SOURCE 380 - 400 - 415 V / 3N / 50 Hz
PERFORMANCE Cooling Heating
Capacity kW 10.6 12.5
BTU / h 36,000 42,700
Air circulation (Hi / Me / Lo) m
3
/h 1,800 / 1,560 / 1,200
Moisture removal (High) Liters/h 4.7 —
ELECTRICAL RATINGS
Voltage rating V 380 400 415 380 400 415
Available voltage range V 342 – 456 342 – 456
Running amperes* A 7.01 7.02 7.06 5.4 5.2 5.1
Max. running amperes** A 7.86 7.88 7.91 6 6 5.9
Power input kW 3.92 3.97 4.02 3.16 3.19 3.23
Power factor % 85 81.6 79.2 88.9 88.5 88.1
C.O.P W / W 2.7 2.67 2.64 3.96 3.92 3.87
Max. starting amperes A 47 49 50 47 49 50
FEATURES
Controls / Thermostat control Microprocessor / I.C. thermostat
Timer ON / OFF 72-hours ON/OFF 24-hours & Program
Fan speeds Indoor / Outdoor 3 and Automatic control / 3 (Auto)
Airflow direction (Indoor) Automatic (Remote control)
Air filter Washable, easy access, long life (2,500 hr)
Remote controller (Option) Wired : REM HW A Wireless : REM HL A
Refrigerant control Electronic expansion valve
Drain pump (Drain connection) No (20A, OD26 mm)
Compressor Scroll (Sanyo)
Operation sound
Indoor - Hi/Me/Lo
dB - A 42 / 40 / 35
Outdoor - Hi
dB - A 53
Color (Approximate value) Indoor Munsell 10Y9.3 / 0.4, RAL 9010-GL
Outdoor Munsell 5Y8.4 / 0.5, RAL 9002-GL
REFRIGERANT TUBING
Limit of tubing length m (ft.) 50 (164 )
Limit of tubing length at shipment m (ft.) 30 ( 98 )
Limit of elevation difference m (ft.) Outdoor unit is higher than indoor unit : 50 (164)
between the two units Outdoor unit is lower than indoor unit : 30 (98)
Refrigerant tube Narrow tube mm (in.) 9.52 (3 / 8)
outer diameter Wide tube mm (in.) 19.05 (3 / 4)
Refrigerant amount at shipment kg R407C - 4.0
DIMENSIONS & WEIGHT Indoor unit Outdoor unit
Unit dimensions Height mm (in.) 240 ( 9 - 14 / 32) 1,235 (48 - 20 / 32)
Width mm (in.) 1,575 (62 ) 940 (37 )
Depth mm (in.) 670 (26 - 12 / 32) 340 (13 - 12 / 32)
Package dimensions Height mm (in.) 317 (12 - 15 / 32) 1,326 (52 - 7 / 32)
Width mm (in.) 1,678 (66 - 2 / 32) 1,016 (40 )
Depth mm (in.) 789 (31 - 2 / 32) 416 (16 - 12 / 32)
Net weight kg (lb.) 38 ( 84) 106 ( 234)
Shipping weight kg (lb.) 44 ( 97) 113 ( 249)
Shipping volume
m
3
(cu. ft)
0.42 (14.8) 0.56 (19.8)