1 Main switch Before starting any maintenance work: Switch off the entire system
The power to all components is switched off.
2 Stop button If the system overheats: Switch off the boiler
The pumps continue to run
CAUTION! Always turn off the heating using the STOP button.
Never use the main switch.
3 Door switch Switches the induced draught fan to full speed if the door is opened while
the boiler is running
4 Safety overload switches,
motor overload switch
Switch off the related component in the event of fault currents or overloads
5 Power supply fuses Properly fuse the control system and any electronic components
F1 Primary transformer 800 mAT
F2 Power supply 5 VDC 1.6 AT
F3 Power supply +15 VDC 200 mAT
F4 Power supply -15 VDC 200 mAT
F5 Power supply 24 VDC 2.0 AT
F6 Power supply 12 VDC 3.15 AT
When changing fuses, fit fuses with the rated current specified.
6 Motherboard fuse Motherboard fuse 5 AT
When changing the fuse, fit a fuse with the rated current specified.
5 Devices for preventing the boiler from overheating
A Boiler controller Switches the boiler and feed off if the boiler temperature reaches a prede‐
fined value (default 5°C) above the boiler temperature setpoint.
B Thermal discharge safety device At a temperature of around 100°C a valve opens and sends cold water to
the safety heat-exchanger (safety battery) to reduce the temperature.
C Safety temperature limiter
(STL)
Switches off the blower fan at a maximum boiler temperature of 105°C.
The pumps continue to run.
Once the temperature falls to below approx. 75°C, the STL can be reset
mechanically:
Unscrew the cap on the safety temperature limiter
Reset the safety temperature limiter by pressing with a screwdriver
D Safety valve
(not illustrated, provided by the custom‐
er)
When the boiler pressure is too high, the safety valve opens and vents off
the hot water as steam.
Before you start up the system again, top up the system to replace
any water which has been lost through venting.
2
Safety
Safety devices
16 Froling GesmbH | A-4710 Grieskirchen, Industriestraße 12 | www.froeling.com