Sharp QT-80W Instruction Manual Page 74

  • Download
  • Add to my manuals
  • Print
  • Page
    / 93
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 73
73
7.1.5 QT-FQ…F/CW
-21 mm height-
ECG-type Seque
nce
PIN
1
PIN
2
PIN
3
PIN
4
PIN
5
PIN
6
PIN
7
QT-FQ 1x24-39 F/CW
1-7
2 2 1 1
QT-FQ 1x54 F/CW
1-7
2 2 1 1
QT-FQ 1x80 F/CW
1-7
2 2 1 1
QT-FQ 2x24-39 F/CW
1-7
1 1 2 2 2 2
QT-FQ 2x54 F/CW
1-7
1 1 2 2 2 2
QT-FQ 2x80
1-7
1 1 2 2 2 2
7.1.6 QT-FC
ECG-type Seque
nce
PIN
1
PIN
2
PIN
3
PIN
4
PIN
5
PIN
6
PIN
7
QT-FC 1x55/230-240 S
1-4
2 2 1 1
7.2 Terminal Types
WAGO 250 WAGO 251 WAGO 251-
mini
QT-FH MULTI CW X
QT-FQ … CW X
QT-FH 1x14, 21 X
QT-FH 3, 4x14 X
QT-FH...F/CW X
QT-FQ...F/CW X
QTi X
Special features of particular terminals: see Section 3.1ff
7.3 Inrush Currents
QUICKTRONIC
®
INTELLIGENT
Max. number of ECGs
with automatic circuit
breakers
Ip[A] T
H
[µs] 10A 16A
QTi 1x14/24/21/39
1 155 26 41
QTi 1x28/54
1 155 26 41
QTi 1x35/49/80
1 155 26 41
QTi 2x14/24/21/39
1 200 19 31
QTi 2x28/54
1 200 19 31
QTi 2x35/49
1 200 19 31
QT-FQ 2x80
60 230 5 9
QUICKTRONIC
®
21 mm height
Max. number of ECGs
with automatic circuit
breakers
Ip[A] T
H
[µs] 10A 16A
QT-FH 1x14-35 F/CW
17 155 25 41
QT-FH 2x14-28 F/CW
20 210 17 28
QT-FQ 1x24-39 F/CW
17 155 25 41
QT-FQ 1x54 F/CW
27 170 17 28
QT-FQ 1x80 F/CW
27 170 17 28
QT-FQ 2x24-39 F/CW
27 170 17 28
QT-FQ 2x54 F/CW
32 210 10 17
QT-FQ 2x80 F/CW
39 260 8 14
Page view 73