STANDARD SPECIFICATION - BUILDINGS
DPI REFERENCE TEXT - APRIL 2009
PAGE 33
ELECTRICAL INSTALLATIONS
Appliances
Gas water heaters: To AS 4552.
Gas space heating appliances: To AS 4553.
Commissioning
On completion of installation and testing, turn on
isolating and control valves and purge and charge
the installation.
Compliance plate - Hold Point
Hold Point: Install a compliance plate and provide a
certicate of approval prior to practical completion.
17. ELECTRICAL INSTALLATIONS
17.1 GENERAL
Cross reference
Refer to the Site preparation section for service
trenches.
Standards
Electrical installations generally: To AS/NZS 3000
and SAA HB 301.
Domestic electrical installations: To AS 3006.
Selection of Cables: To AS/NZS 3008.1.1
Design: To SAA HB 301
Minimum energy performance standards:
To AS/NZS 4782.2 and AS/NZS 4783.2
Regulations
Comply with the following Regulations:
- PowerWater Regulations
- WorkSafe Requirements (O, H & S Regulations)
- The B.C.A.
- DPI, Safety and Technical Regulations
- The N.T. Electricity Reform Act.
Materials & Components
Luminaries: To AS/NZS 60598.1.
Circuit breakers: To AS 60947.2.
Low voltage switchgear and control gear:To
AS 60947.1.
Switchboards: To AS 3439.1 or AS 3439.3 as
appropriate.
Domestic electricity meter enclosures: To AS 6002
and PowerWater requirements.
Cables: To AS/NZS 3008.1.1.
17.2 INSPECTION
Notice - Witness Point
Witness Point: Give sufcient notice so that
inspection may be made of trench excavations
and underground or concealed conduits or cables
before covering.
17.3 INSTALLATION GENERALLY
Wiring: Conceal cables and conduits, including
underground cable or conduit entering the building,
in a manner that will allow wiring replacement
without structural work or the removal of cladding or
lining. Do not penetrate damp-proof courses.
Electrical accessories: Install ush mounted
accessories in wall boxes, if required, in masonry
and in mounting brackets in stud walls.
Fixed appliances: Provide connections with socket
outlet and ush blank plate for xed and stationary
appliances.
17.4 CONSUMER MAINS & METERING
General: Provide a consumer main and connect to
the main service.
Meter Box: Provide a metal meter box with a hinged
lid and arrange for the Kwh meter to be installed by
PowerWater.
Standard: To AS 6002 and PowerWater
requirements.
17.5 DISTRIBUTION BOARD
General: Provide control switchgear, circuit
breakers and residual current devices (RCD’s) on a
wall mounted distribution board enclosed in a case
with a hinged door.
Housing: Install a distribution board with a minimum
of 4 spare poles.
Circuit Breakers: DIN rail mounted. 6kA minimum
fault current rating. Size circuit breakers to the
calculated fault current at the site. Provide combined
circuit breakers and residual current devices on
each circuit requiring RCD protection.
Leave documents and instructions behind for use
by the building occupiers on how to use the RCD’s.
17.6 ACCESSORIES
Socket outlets and light switches
Proprietary Item: Use Clipsal 2000 series or HPM
Excel. For Public Housing or institutional buildings
use single piece face plates and positively locked
in switches.
Mounting heights
Light Switches and Fan Controllers: 1300 AFL.
Generally 1000 AFL if required for disabled access
which must match the height of the door furniture.
Socket Outlets: Generally 300 above oor level or
or 200 above bench surface.
Ceiling Fans
Mounting Height: 2300 mm minimun.
Fixing: x to 75 x 50 hardwood trimers securely
xed between truss bottom chords. On sloping
ceilings provide a hardwood mounting block to give
a horizontal xing.
Controls: 5 speed or electronic generally mounted
adjacent to light switches and in view of the fan.