14 Rockwell Automation Publication PFLEX-IN020C-EN-P - July 2013
PowerFlex 700S and 700H Frames 10...14 IP00, NEMA/UL Open Power Structures
Ventilation
The ventilation openings must fulfill the requirements set by the selected IP class.
The examples in this manual apply to protection class IP21. Ta b l e 9
contains the
minimum required air opening dimensions. Refer to Figure 7
for the location of
the openings as indicated in the table below.
Table 9 - IP21 Ventilation Opening Minimum Requirements
Figure 7 - Enclosure Ventilation Example
Opening Purpose Enclosure Width
(1)
(1) Refer to Enclosure Requirements on page 9 for the required enclosure widths for each drive frame size.
600 mm (23.6 in.) 800 mm (31.5 in.)
Area for cool air intake 130,050 mm
2
195,075 mm
2
Area for hot air exhaust 70,000 mm
2
105,000 mm
2
A
A
Comments to this Manuals