77
Safety Devices Data - Heatpump
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
1) ALL SPECIFICATIONS ARE SUBJECTED TO CHANGE BY THE MANUFACTURER WITHOUT PRIOR NOTICE.
OPEN Pa / psi
CLOSE Pa / psi
OPEN Pa / psi
CLOSE Pa / psi
DISCHARGE THERMOSTAT SETTING °C / °F
OPEN Pa / psi
CLOSE Pa / psi
OPEN Pa / psi
CLOSE Pa / psi
DISCHARGE THERMOSTAT SETTING °C / °F
125 / 257
MODEL
INDOOR UNIT MDB400BR4
OUTDOOR UNIT MMC100BR x 4
SAFETY DEVICE
HIGH PRESSURE SWITCH
TYPE
AUTO RESET
3240536 / 470
2647587 / 384
LOW PRESSURE SWITCH
TYPE AUTO RESET
124105.6 / 18
193053.2 / 28
PHASE SEQUENCER OYLT
MODEL
INDOOR UNIT MDB500BR4
OUTDOOR UNIT MMC125BR x 4
SAFETY DEVICE
HIGH PRESSURE SWITCH
TYPE AUTO RESET
3240536 / 470
2647587 / 384
LOW PRESSURE SWITCH
TYPE
AUTO RESET
124105.6 / 18
193053.2 / 28
PHASE SEQUENCER OYLT
125 / 257
Page view 78